Evaporative Condensers

cATC Evaporative Condenser

cATC Evaporative Condenser

The cATC line of evaporative condensers represents Evapco’s commitment to product development. The line is comprised of 24 models ranging in size from 128 to 357 nominal ammonia tons (551 kW to 1,538 kW). The induced draft counterflow condensers are designed especially for easy maintenance and long, trouble-free operation.

The cATC Evaporative Condenser is an Advanced Technology, induced draft counterflow design condenser featuring EVAPCO’s patented THERMAL-PAK ® COIL – the most efficient in the industry. The counterflow design provides the cATC Evaporative Condenser with inherently better operational and maintenance features. These features are described below.

Principle of Operation

The refrigerant is circulated through the coil of the evaporative condenser. Heat from the refrigerant is dissipated through the coil tubes to the water cascading downward over the tubes. Simultaneously, air is drawn in through the air inlet louvers at the base of the condenser and travels upward over the coil opposite the water flow. A small portion of the water is evaporated which removes the heat. The warm moist air is drawn to the top of the evaporative condenser by the fan and is discharged to the atmosphere. The remaining water falls to the sump at the bottom of the condenser where it is recirculated by the pump up through the water distribution system and back down over the coils.

Thermal-Pak II Coil

EVAPCO's Thermal-Pak II ® coils feature a patented design which assures maximum cooling capacity. The airflow through the coil is counterflow to the fluid flow, providing the most efficient heat transfer process. A special coil design is utilized to reduce the air pressure drop through the unit while maximizing tube surface area and increasing its heat transfer capabilities. The uniquely shaped tubes of the coil are staggered in the direction of airflow to obtain a high film coefficient.

The coils are manufactured from high quality steel tubing following the most stringent quality control procedures. Each circuit is inspected to assure the material quality and then tested before being assembled into a coil. Finally, the assembled coil is pneumatically tested at 400 psig (2758 kPa) under water to ensure it is leak free.

To protect the coil against corrosion, it is placed in a heavy steel frame and then the entire assembly is dipped in molten zinc (hot-dip galvanized) at a temperature of approximately 800°F (427º).

Efficient Drift Eliminators

An extremely efficient drift eliminator system is standard on the cATC evaporative condenser. The system removes entrained water droplets from the air stream to limit the drift rate to less than 0.001% of the recirculating water rate. With a low drift rate, the cATC Evaporative Condenser saves valuable water and water treatment chemicals. The cATC Evaporative Condenser can be located in areas where minimum water carryover is critical, such as parking lots.

The drift eliminators are constructed of an inert polyvinyl chloride (PVC) plastic material which effectively eliminates corrosion of these vital components. They are assembled in sections to facilitate easy removal for inspection of the water distribution system.

Superior Air Inlet Louver and Screen Design

The air inlet louver screens on the cATC are constructed of corrosion-free PVC. They are a two pass design that minimizes splashout and reduces the potential for algae formation inside the condenser.

In single pass louver systems used by other manufacturers, circulating water droplets tend to splashout, especially when the fans are shut off. With the two pass louver system, the water droplets are captured on the inward sloping pass, minimizing splashout problems.

This unique louver design completely encloses the basin area. Direct sunlight is blocked from the water inside the condenser, thereby reducing the potential of algae formation. Water treatment and maintenance costs are substantially reduced.

While effectively containing the recirculating water and blocking sunlight, the louver design has a low pressure drop. The low pressure drop results in lower fan energy consumption, which reduces the operating costs of the condenser.

Pressurized Water Distribution System

EVAPCO's Zero Maintenance ZMII® Spray Nozzle remains clogfree while providing even and constant water distribution for reliable, scale-free evaporative cooling under all operating conditions. The heavy duty nylon ZM® Spray nozzles have a 1-5/16" diameter opening and a 1-1/2" splash plate clearance. Furthermore, the fixed position ZM® nozzles are mounted in corrosion-free PVC water distribution pipes that have threaded end caps. Together, these elements combine to provide unequaled coil coverage and scale prevention, and make the industry's best performing non-corrosive, maintenance-free water distribution system 

The water distribution is designed to provide a minimum 6 GPM over each square foot (4 liters per second over each square meter) of unit plan area to ensure proper flooding of the coil.

Fast, On-Time Shipments

The cATC is a completely factory assembled evaporative condenser manufactured by a dedicated professional workforce, expert in building evaporative evaporative condensers. Factory trained mechanics and EVAPCO's strict quality control and inspection procedures guarantee the quality of every unit shipped.

EVAPCO's controlled factory environment ensures fast on-time shipments, allowing the cATC to be available WHEN THE CUSTOMER WANTS IT!

Designed for easy access, the cATC Evaporative Condenser leads the industry in maintenance friendly features. The three most critical areas for evaporative condenser maintenance are the basin, drive system, and coil. The cATC basin section is designed to allow quick and easy access from outside the condenser. Just like the basin, all service to the drive system can be safely performed from the side of the condenser, and EVAPCO’s Power-Band drive system is the easiest belt drive system to maintain in the industry! The exclusive Thermal-Pak® Coil is designed for trouble-free maintenance and long life straight from the factory. 

Easy Access

The cold water basin section is easily accessible from ground level by simply removing the (2) two Quick Release Fasteners on the inlet louver assemblies surrounding the evaporative condenser and lifting out the lightweight louver.

The basin can be accessed from all (4) four sides of the condenser. This open basin design enables the cATC basin to be easily cleaned.

Clean Pan Basin Design

The cATC features a sloped basin from the upper to lower pan section. This “Clean Pan” design allows the water to be completely drained from the basin. The evaporative condensers water will drain from the upper section to the depressed lower pan section where the dirt and debris can be easily flushed out through the drain. This design helps prevent buildup of sedimentary deposits, biological films and minimizes standing water.

Stainless Steel Strainers

The EVAPCO standard for many years, the stainless steel strainer is one component of the evaporative condenser subject to excessive wear and corrosion. With stainless steel construction, this component will last the life of the cooling tower.

Thermal-Pak II Coil

EVAPCO’s exclusive elliptical Thermal-Pak II ® coil is manufactured at EVAPCO from high quality steel tubing following the most stringent quality control procedures. Each circuit is inspected to assure the highest material quality and then is tested at 400 psig (2758 kPa) under water to ensure it is leak free. To protect the coil against corrosion, it is placed in a heavy steel frame and then the entire assembly is dipped in molten zinc (hot-dip galvanized) at a temperature of approximately 800º F (427º C). The tubes are pitched in the direction of fluid flow to provide good liquid drainage.

Easy, Removable Air Inlet Louvers with Quick Release Fasteners

The cATC features a Quick Release Fastener design consisting of (2) two large thumbscrews and a latch system. By loosening the thumbscrews, the latch pulls up and out of the louver frame, allowing the louver to be removed while the latch and thumbscrews stay on the evaporative condensers.

Motor Mount, Power Band Belt Adjustment and Bearing Lubrication

The fan motor and drive assembly are designed to allow easy servicing of the motor and adjustment of the belt tension from the exterior of the unit. The T.E.F.C fan motor is mounted on the outside on these models and is protected from the weather by a cover which swings away for maintenance.

A large hinged access door is located on the side of the unit for easy access to the fan drive system. The belt can be adjusted by tightening the J-Bolts on the motor base and the tension can be checked easily through the access door, all while standing at the side of the unit. The bearings can also be lubricated from the side of the unit. The bearing lubrication lines have been extended to the exterior casing and are located by the access door, thus making bearing lubrication easy.

Sloped access ladders and working platforms are available as an option to facilitate maintenance.

Go to Optional Equipment for details.

The cATC Evaporative Condenser features the highly successful EVAPCO POWER-BAND Belt Drive System engineered for heavy-duty operation. The POWER-BAND Drive System has consistently provided trouble-free operation in the most severe duty evaporative condenser applications. In addition, the complete drive system including the fan motor is standard with a (5) Five Year Warranty. Fan Motors Power-Brand Belt Drive Drive System Sheaves Fan Shaft Bearings (5) Five Year Warranty 

Fan Motors

All cATC Evaporative Condenser models utilize heavy duty totally enclosed (T.E.F.C.) fan motors designed specifically for evaporative condenser applications. In addition to the standard motors offered on each evaporative condenser, EVAPCO offers many optional motors to meet your specific needs, including:

  • Premium Efficiency Motors
  • Multi-Speed Motors

cATC models feature T.E.F.C. motors are located on the outside of the unit, protected by a hinged, swing away cover.

Power-Band Belt Drive

The Power-Band drive is a solid-back multigroove belt system that has high lateral rigidity. The belt is designed for evaporative condenser service, and is constructed of neoprene with polyester cords. The drive belt is sized for 150 percent of the motor nameplate horsepower ensuring long and trouble free operation.

Drive System Sheaves

Drive system sheaves located in the warm, moist atmosphere inside the cooling tower are constructed of an aluminum alloy. Those located externally are protected by a hinged cover.

Fan Shaft Bearings

 

The fan shaft bearings on the cATC Evaporative Condenser are specially selected to provide long life, minimizing costly downtime. They are rated for an L-10 life of 75,000 to 135,000 hours, making them the heaviest duty pillow block bearing in the industry used for Evaporative Condenser duty.

Year (5) Drive Warranty

EVAPCO provides a standard five (5) year motor and drive warranty on all direct drive Power-Band belt drive and optional gear drive cATC Evaporative Condensers. This unique warranty is designed to offer the end user optimum protection against fan drive and motor failure. It is a comprehensive plan which includes the fan, fan shaft, sheaves, fan bearings, belts, gear box, flexible coupling, driveshaft and the motor.

The standard design of the EVAPCO cATC provides the customer with the most efficient and easiest Evaporative Condenser to maintain in the industry. There are additional options which can make maintenance easier, extend the life, or enhance the performance capabilities of the Evaporative Condenser. These options are listed below. 

Evapco Manufactured 304 Stainless Steel Coils

The Evapco manufactured Stainless Steel Coil is an elliptical tube, continuous return bend, 304 stainless steel coil. It is available in both the Patented Thermal Pak Coil design used on AT, UB, LR and LS coolers and condensers and in the patent pending SensiCoil design used in the ESWA. This option has superior corrosion resistance for Open Systems and Hostile Environments and is available with the Standard Evapco Lead Time! For more detail on the corrosion resistant properties of 304 stainless steel, see Evapco's MaintenanceInstruction Bulletin, 112AA. 

The Evapco 304 SST coil option can be manufactured as an ASME coil and is CTI certified on the ESWA and ATWB closed circuit cooler.

Sloped Access Ladders

A sloped access ladder is available for all cATC models. The EVAPCO designed access ladder features a sloped “ships type” ladder arrangement which provides fast and easy access to the water distribution system and drive components. A grab bar is attached to the sloped ladder for safe and easy ascent and descent. There is no need for safety cages or railings with this design. The ladder(s) will ship loose and must be field mounted. The sloped ladder meets all applicable OSHA requirements.

Extended Surface Coil

Evaporative Condensers can be provided with spiral fins on the heat exchanger coil to increase the dry performance of the unit. Dry performance is accomplished by rejecting heat to the atmosphere without the use of the spray pump and the evaporation process. Dry operation can be practical in cold climates and/or when reduced winter loads exist. The number of fins per inch and and quantity of rows finned can be varied to obtain different dry performances.

Electric Heaters

Electric immersion heaters are available as an option and are located in the basin of the condenser. They are sized to maintain a +40° F (4,4º C) pan water temperature at 0°F (-18º C) ambient with the fans off *. They are furnished with a combination thermostat/low water protection device to cycle the heater on when required and to prevent the heater elements from energizing unless they are completely submerged. All components are enclosed in rugged, weather proof enclosures for outdoor use. Heater control packages that include contactor, transformer or disconnects are available.

(*) - Electric heater selection based on 0°F (-18º C) ambient temperature. For alternate low ambient heater selections consult the factory.

Stainless Steel Water Touch Basin

The cATC Evaporative Condenser has a modular design which allows specific areas to be enhanced for increased corrosion protection. The basin area of the condenser experiences turbulent mixing of air and water, in addition to silt build-up. In conjunction with the EVAPCOAT Corrosion Protection System, EVAPCO offers an optional Stainless Steel Water Touch Basin. This option provides Type 304 or Type 316 stainless steel for the entire basin area including the support columns of the evaporative condenser and the louver frames.

The basin section provides the structural support for the unit and is a critical part of the condenser. The Stainless Steel Water Touch Basin provides maximum corrosion protection.

Other Options

  • Hot Water or Steam Coils

  • Steam Injectors

  • Vibration Switches

  • Remote Sump Configuration

  • A.S.M.E. Condensing Coils

  • C.R.N. Condensing Coils

  • Additional Stainless Steel Options 

  • Motors– Energy Efficient / Inverter Duty / 2S/1W and 2S/2W / Mill and Chem Duty Automotive Duty and Many More, Consult the Factory

Electric Water-Level Control

EVAPCO evaporative condensers are available with an optional electric water level control system in place of the standard mechanical makeup valve and float assembly. This package provides very accurate control for the basin water level and does not require field adjustment, even under varying operating conditions.

The control was designed by EVAPCO and is manufactured exclusively for EVAPCO. It consists of multiple heavy duty stainless steel electrodes. These electrodes are mounted external to the unit in a vertical stand pipe. For winter operation, the stand pipe must be wrapped with electric heating cable and insulated to protect it from freezing.

The weather protected slow closing solenoid valve(s) for the makeup water connection is factory supplied and is ready for piping to a water supply with a pressure between 25 and 50 psig (138 kPa and 345 kPa).

Furnish and install, as shown on the plans, an Evapco model _________ induced draft, counterflow evaporative condenser with a condensing capacity of _________ kW total heat of rejection when operating with _________ refrigerant at ______ (ºC) condensing temperature with a ______ (ºC) design wet bulb temperature.

Basin and Casing

The basin and casing shall be constructed of G-235  hot-dip galvanized steel for long life and durability. Standard basin accessories shall include overflow, drain, type 304 stainless steel strainers, and brass make-up valve with plastic float.

Belt Drive

Fan Motor

_________ kW totally enclosed air over ball bearing fan motor(s) shall be furnished suitable for service on _________ volts, _________ hertz, and _________ phase. Motor(s) shall be mounted on an adjustable base which allows the motor to swing to the outside of the unit for servicing.

Drive

The fan drive shall be a multigroove, solid back V-belt type with taper lock sheaves designed for 150% of the motor nameplate horsepower. The belt material shall be neoprene reinforced with polyester cord and specifically designed for evaporative condenser service. Fan and motor sheaves shall be aluminum alloy construction. The fans and fan sheaves shall be mounted on the shaft with a specially coated bushing to provide maximum corrosion protection. Belt adjustment shall be accomplished from the exterior of the unit. Bearing lube lines shall be extended to the exterior of the unit for easy maintenance.

Axial Propeller Fans

Fans

shall be heavy duty axial propeller type statically balanced. The fans shall be constructed of aluminum alloy blades, installed in a closely fitted cowl with venturi air inlet. Fan screens shall be galvanized steel mesh and frame, bolted to the fan cowl.

Fan Shaft Bearings

Fan shaft bearings shall be heavy duty self-aligning ball type with grease fittings extended to the outside of the unit. Materials shall be stainless steel balls with chrome steel races and zinc plated housing for corrosion resistance. Bearings shall be designed for a minimum L-10 life of 75,000 hours.

Water Recirculation Pump

The pump(s) shall be a close-coupled, centrifugal type with mechanical seal, installed vertically at the factory to allow free drainage on shut down. _________ kW totally enclosed motor(s) shall be furnished suitable for outdoor service on _________ volts, _________ hertz, and _________ phase.

Heat Transfer Coil

Condensing coil(s) shall be all prime surface steel, encased in a steel framework and hot-dip galvanized after fabrication as a complete assembly. The tubes shall be arranged in a self-spacing, staggered pattern in the direction of airflow for maximum heat transfer efficiency and minimum pressure drop, without the use of additional spacers between the coil tubes. The coil(s) shall be designed with sloping tubes for free drainage of liquid refrigerant and shall be pneumatically tested at 400 psig (2758 kPa), under water.

Water Distribution System

The system shall provide a water flow rate of not less than 6 GPM over each square foot (4 liters per second over each square meter) of unit face area to ensure proper flooding of the coil. The spray header shall be constructed of schedule 40 polyvinyl chloride pipe for corrosion resistance. All spray branches shall be removable for cleaning. The water shall be distributed over the entire coil surface by heavy-duty molded nylon ZM spray nozzles (33.3mm orifice)  with internal sludge ring to eliminate clogging. Nozzles shall be threaded into spray header to provide easy removal for maintenance.

Eliminators

The eliminators shall be constructed entirely of inert polyvinyl chloride (PVC) in easily handled sections. The eliminator design shall incorporate three changes in air direction to assure complete removal of all entrained moisture from the discharge air stream. Maximum drift rate shall be less than 0.001% of the circulating water rate.

Louvers

The louvers shall be constructed from polyvinyl chloride (PVC). The louvers shall be mounted in easily removable frames for access to the pan for maintenance. The louvers shall have a minimum of two changes in air direction to prevent splashout and block direct sunlight.

Finish

All basin and casing materials shall be constructed of G-235 heavy gauge mill hot-dip galvanized steel. During fabrication, all panel edges shall be coated with a 95% pure zinc-rich compound for superior protection against corrosion.